AquaPump Hybrid
Integrated monobloc boiler and heat pump system.
A single system with integrated Smart control that allows the user to intelligently optimise energy production based on the external temperature values and the immediate utilisation needs.
Designed for the production of hot and cold water for industrial and tertiary environments using renewable energy, this system integrates the high efficiency of the condensing technology (34 kW boiler with modulating premix burner with NOx emission class 6) with the performance of the latest generation air-to-water heat pump with inverter technology at 14 kW in warming operation and 12 kW in cooling operation.
Technical characteristics
Condensing boiler:
- Premixed burner with low NOx polluting emissions, class 6 according to EN15502-1.
- Low carbon stainless steel heat exchanger.
- Sealed combustion chamber.
- Forced flue gas outlet.
- Integrated condensate drain.
- Control and safety equipment.
- Electronic ignition.
- Electronic equipment and microprocessor with self-testing that manages all burner control and verification operations.
Inverter heat pump:
- DC inverter fan motor.
- Twin Rotary DC inverter compressor with permanent magnets.
- R32 Refrigerant gas.
- Source heat exchanger with finned battery with copper tubes and aluminium fins with hydrophilic treatment.
Hydraulic circuit:
- Pressure gauge to check the system’s pressure.
- NTC probes for water regulation.
- Hydraulic circuit temperature control thermometer.
- Flow meter for measuring the system’s water flow rate.
- Brushless circulation pump with DC motor, variable flow rate and built-in automatic air separator (degasser).
- 90°C Safety thermostat.
- 3 bar system safety valve.
- IPX5D Protection rating.
- 8-litre expansion reservoir.
Request information
Card Specifications
AquaPump Hybrid
MODEL | MAX HEAT OUTPUT in HEATING kW | MAX HEAT OUTPUT in COOLING kW | POWER SUPPLY V/Hz | WEIGHT kg |
---|---|---|---|---|
HYN432IT | 34,8 | 12,05 | V/Hz 230V/1/50Hz | 170 |
HYN532IT | 34,8 | 12,05 | V/Hz 400V/3/50Hz | 170 |
Nominal Performances in Heating
MODEL | MAX HEAT OUTPUT * kW | MAX AIR FLOW m3/h | WATER TEMPERATURE DIFFERENTIAL °C | WATER FLOW RATE l/h |
---|---|---|---|---|
AB018IT-HY | 17 | 3000 | 60-35 | 600 |
AB034IT-HY | 34 | 7000 | 60-35 | 650 |
Nominal Performances in Cooling
MODEL | MAX HEAT OUTPUT * kW | MAX AIR FLOW m3/h | WATER TEMPERATURE DIFFERENTIAL °C | NOISE LEVEL 5 m | POWER SUPPLY V/Hz | POWER SUPPLY V/Hz |
---|---|---|---|---|---|---|
AB018IT-HY | 8,8 | 1600 | 7-12 | range max dB(A) 55.7 | 230/V/1/50 | 28 |
AB034IT-HY | 13 | 4050 | 7-12 | range max dB(A) 63.2 | 230/V/1/50 | 45 |